INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624
Approved Document No: GLT-211-7-1
Issue 1.0 Author: MG Date: 22/1/2013 PAGE 17
11 OTHER CONNECTIONS
11.1 Repeater connection
The Infinity ID2 has an RS485 connection for a serial repeater. The repeaters has full control. Up to 3 repeater
can be powered from the Aux 24V DC output on the panel. If 4 or more are to be connected, then they must be
powered from external 24V power supplies. The panel supports up to 8 repeaters.
ID2 PANEL ID2 REPEATER
ID2 Panel
ID2 Repeater
Description
AUX 28V +
24V DC IN +
Power for repeater
AUX 28V 1
24V DC IN -
Power for repeater
RS485 B
RS485 B
Data connection
RS485 A
RS485 A
Data connection
RS485 GND
RS485 GND
Data connection screen