INFINITY ID2 INSTALLATION MANUAL. Software Versions: PANEL O.X-R8629 & LOOP O.J-R8624
Approved Document No: GLT-211-7-1
Issue 1.0 Author: MG Date: 22/1/2013 PAGE 32
19.4 Supply faults
19.5 Earth faults
An EARTH fault indicates that something is shorting to earth
(usually through the cable screen). Disconnect the earth
screens one at a time to determine the problem line.
(Note: connecting other equipment , eg an oscilloscope or a PC , to
the panel can give an earth fault)
The Screen will indicate if it is a Positive or Negative voltage shorting to earth (Earth Fault Pos or Earth Fault
Neg).
***DO NOT DISCONNECT THE MAINS EARTH CONNECTION. THIS WILL CAUSE A PROBLEM WITH THE
PANELS OPERATION***
19.6 Double address
This indicates that a double address has been detected. This usually happens during initial setup, where 2
detectors are given the same address, or if a head is replaced during maintenance, and its address has been
wrongly set. In the second scenario, the panel will report 2 fault addresses, one will be the double address, and
the other will be a missing device. As a further aid to finding the fault, the panel will light the LEDs of any
detectors with a double address (Sounders & I/O units will not be indicated as they have no panel controlled
LED to light up)
1. Make a list of the double addresses reported (there may be more than one).
2. Go to view device screen in Configuration menu 1. Scroll through the devices, and make a list of any
that are missing (Note: the panel skips over empty addresses when scrolling)
3. Go to the location of the missing device, and check if it has its LED on (Detector), or check the dip
switch setting.
4. If this does not cure all double addresses, go to the known location, and temporarily remove the device.
The panel will now report the type of device that was also configured to this address from the view
device screen. This will help narrow down the search for the device. (eg if extra device is call point,
check the address settings of all the call points)
19.7 System fault
A system fault is an abnormal microprocessor running condition due to various unexpected phenomena.
This will result in the panel attempting to correct itself. Should this fault occur, the System Fault LED, General
Fault LED, General Fault relay and fault internal buzzer will be constantly active until the control keyswitch is
turned from off position to control enable position. This should cause this fault condition to reset. If not, consult
your supplier.
*** FAULT ***
1 of 1
Earth Fault Pos